Saturn Pyro Sdn Bhd
Johor Bahru Office

44 & 44A, Jalan Palma Rafis 1,
Taman Dato Chellam,
81800 Ulu Tiram,
Johor, Malaysia.
+607-8660510
+607-8660511
enquiry@saturnpyro.com

Shah Alam Office
K03-03-12, Tower 3,
UOA Business Park,
No 1, Jalan
Pengaturcara U1/51A,
Section U1, Kawasan
Perindustrian Temasya,
40150 Shah Alam,
Selangor, Malaysia.
+607-8660510
+607-8660511
desmond@saturnpyro.com

Penang Office
Penthouse 1-21-1,
Suntech @ Penang Cybercity
Lintang Mayang Pasir 3,
11950 Bayan Baru,
Penang, Malaysia.
+607-8660510
+607-8660511
desmond@saturnpyro.com

Singapore Office
Saturn Pyro Pte Ltd
101 Kitchener Road,
#02-42 Jalan Besar Plaza,
Singapore 208511.
+607-8660510
+607-8660511
jerry@saturnpyro.com
 
India Office
3, Gr Floor, Eishita,
Shiv Vallabh Cross Road,
Ashokvan, Dahisar (E.),
Mumbai 400068.
+91 22284 84682
+91 98191 56654

AR5-L

Previous 8 / 8 Next

AR5-L Portable Power Analyzers


Download Files

AR5L_Part1.pdf (888.68 KB)
AR5L_Part2.pdf (0.93 MB)
Portable single and three-phase power analyzer

Product Description

The AR5L portable analyzer increases the benefits of the CIR-e family as it has a display screen and records the measured parameters in 2 or 4 quadrants. It has an internal memory that stores the electrical parameters for subsequent downloading onto a computer via the communications cable.

It allows for the selection of variables to be recorded, as well as the recording period and the starting conditions for recording the measured parameters.

It has several operating programs running in order to perform harmonic studies, quality reports, flicker measurements, checking leakage currents and earth leakage relays, among others.

The unit's recorded data is compatible with the programs Power Vision and Power Vision Plus.

Features:
  • Measures all of the main electrical parameters of an electricity network
  • Measurement in true root mean square
  • Built-in energy meter
  • With 4 voltage channels and 4 current channels (AR5-L)
  • Configurable auto-trigger, depending on the parameters required
  • Languages: Spanish and English
  • Large backlit LCD display
  • CAT III 600 V (EN 61010). UL Certificate
  • Display of up to 30 electrical parameters on the screen
  • Small size and reduced weight, only 800 g
  • Independent files for each measurement
  • Including the powerful analysis software: POWER VISION PLUS
  • Configurable with menus
  • Optional operation with no external power supply, with an autonomy of up to 8 hours
  • RS-232 Communications with PC
  • Clamp auto-detection
  • Auto-selection of parameters stored
  • Calculation of the time remaining until the memory is full
  • Linear or rotating memory (depending on the configuration)
Application:
  • Complete study of the installation where the analyzer is capable of gathering different types of records: harmonics, disturbances, meter verification, transients, flicker, etc.
AR5L

Specification


Power supply circuit
Through an external power supply unit 100...240 V ac / 12 V dc
Frequency 50...60 Hz
Consumption 15 V·A
Operating temperature 0...+40 ºC
Altitude ≤ 2 000 m
Humidity of operation 80 % for temperatures under 31 ºC, with a linear decrease down to 50 % at 40 ºC
Metering circuit Three-phase (3 wires) Three-phase (3 / 4 wires)
Voltage circuit
Measurement range In accordance with the clamp, 0.01 A...20 kA
Voltage and current transformation ratios Programmable
Measurement units Automatic change of scale
Internal memory 1 Mb
Accuracy class (*)
Voltage 0.5 % ± 2 digits
Current 0.5 % ± 2 digits
Active power 1 % ± 2 digits
Power factor 1 % ± 2 digits
Build features(*)
Housing Reinforced insulation
Keyboard / Display On the front panel
Display LCD 160 x 160 pixels (backlit)
Current clamp connector 3 3 / 4
Dimensions 220 x 60 x 130 mm
Weight 800 g
RS-232 Outputs Series output
Safety Category III - 600 V, in accordance with 61010

Standards
EN 61000-3-2 (1995), Harmonics
EN 61000-3-3 (1995), Voltage fluctuations
EN 61000-6-4 (2002), Industrial emissions
EN 55011 (1994), Driven (EN 52022 – Class B)
EN 55011 (1994), Radiated (EN 55022 – Class A)
EN 61000-6-2 (2022), Industrial immunity
EN 61000-4-2 (1995), Electrostatic discharge
ENV 50140 (1993), Radiated electromagnetic field
EN 61000-4-8 (1995), Rapid transient bursts
ENV 50141 (1993), RF in common mode
EN 61000-4-8 (1995), Magnetic field at 50 Hz
EN 61000-6-1 (2002), Domestic immunity
EN 61000-4-5 (1995), Shockwave
EN 61000-4-11 (1994), Power supply interruptions
(*) Accuracy is given by the following measurement conditions: Exclusion of errors produced by the clamps and external voltage transformers, with a range of temperature of 5 ... 45 ºC and power factor of 0 ... 1
Saturn Pyro is an authorized distributor/reseller in Malaysia. Circutor AR5-L Portable Power Analyzer/ Data Logger / Energy Logger  Malaysia. Available in Penang, KL, Selangor, Johor & anywhere in Malaysia & Singapore.